- Ground loop Isolator
- Output powered from the input loop
- High accuracy
- Galvanic isolation
- High reliability
TxIsoLoop-1 and TxIsoLoop-2 simplify your application and avoid undesirable ground loops by providing single and dual loop galvanic isolation. The 0/4-20 mA input is measured and an identical isolated signal is reproduced at the output. Power is drawn from the 0(4)-20 mA input loop, thus no auxiliary power or external power supply is need.
Recommended for electrical grids where the electric potential difference is a major risk, the TxIsoLoop galvanic isolator works on up to 2 isolated channels and eliminates ground loops, which ensures accuracy and signal safety.
This accessory, which is indispensable for industrial environments operates with a response time of only 2 ms.
MPN 8813020100
Novus TxIsoLoop Datasheet Download
Novus TxIsoLoop Manual Download
- Maximum Input voltage (Vin max.): 32 Vdc
- Voltage Drop (Vdrop): < 3 Vdc
- Output Signal (OUTPUT): 0(4) to 20 mA
- Max. Load (RL): 1450 R
- Accuracy: 0.2 % FS @ 0 a 60 °C / RL= 250 R; 0.3 % FS @ -20 a 75 °C / RL= 250
- Operating current: > 0.1 mA
- Overload: < 40 mA; < 32 Vdc
- Response time: 2 ms @ RL= 250 R
- Isolation: 3000 Vac / 10 s; 240 Vac continuous
- EMC: EN 61326-1
- Ambient temperature range: -20 to + 75 °C
- Humidity: 20 to 90 % RH
- Protection: IP40
- Wire gauge for connections: 0.14 to 1.5 mm²
- Recommended torque: 0.8 Nm
- Terminal blocks injected in Polyamide