Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)
Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)
Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)
  • Load image into Gallery viewer, Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)
  • Load image into Gallery viewer, Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)
  • Load image into Gallery viewer, Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)

Novus N322 - Digital Thermostat On/Off Control - J/K/T Thermocouple RS485 (100-240V)

Vendor
Novus
Regular price
£57.00 (Exc. VAT)
Sale price
£57.00 (Exc. VAT)
Regular price
£68.64 (Exc. VAT)
Sold out
Unit price
per 
Shipping calculated at checkout.

Great For:

  • 2 relay outputs with independent parameters
  • Direct control of elements, compressors, fans and valves
  • RS485 version uses Modbus for remote monitoring
  • Integrates with SCADA, PLC via serial network
  • Simple installation, no SSR required
  • 16A relay with Novus reliability

Typical Uses:

  • Retrofit HVAC
  • Machinery and OEM
  • Catering equipment

Novus N322 J/K/T is a digital temperature controller for heating or cooling purposes with 2 independent setpoints. Operating range -50 to +1000 degrees Celsius with a K Type thermocouple, see below specification for J and T ranges. The output control can be refined with adjustable hysteresis and on/off time delays. With thermostatic control a gentle response can be achieved.

The N322 is a trusted product which will replace or upgrade the majority of manual or programmable thermostats used in industry.

With the RS485 version it is possible to integrate the device into a serial network. Using the Register Table below parameters such as setpoint (SV) and process value (PV) can be read from the devices.

MPN 8032204322

Novus N322 Datasheet Download

Novus N322 Manual Download

Novus N322 Modbus Registers

SIZE: 75 x 33 x 75 mm

PANEL CUTOUT: 70 x 29 mm (+0.5 -0.0 mm)

SUPPLY: 100~240 Vac (± 10 %)

INPUT: Thermocouple J/K/T

OUTPUTS:

OUT1: Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Resistive)

OUT2: Relay: 3 A / 250 Vac, SPST

INPUT SENSOR: The sensor is chosen by the user at the time of purchase and is presented on the upper side of the equipment box.

The options are:

• Thermistor NTC, 10 kΩ @ 25 °C; Range: -50 to 120 °C (-58 to 248 °F); Accuracy:
0.6 °C (1.1 °F);
Maximum error in the interchangeability of original NTC sensors: 0.75 °C (1.35 °F).
This error can be eliminated through the offset parameter of the equipment.
Note: For the NTC thermistor option, the sensor comes with the equipment. Its
operating range is limited to -30 to +105 °C (-222 to +221 °F). It has cable of 3 meters
in length, 2 x 0.5 mm², and can be extended up to 200 meters.
• Pt100; Range: -50 to 300 °C (-58 to 572 °F); α= 0,00385; 3 wires; Accuracy: 0.7 °C (1.3°F); according to IEC-751 standards;
• Thermocouple type J; Range: 0 to 600 °C (32 to 1112 °F); Accuracy: 3 °C (5.4 °F);
• Thermocouple type K; Range -50 to 1000°C (-58 to 1832 °F); Accuracy: 3 °C (5.4 °F);
• Thermocouple type T; Range: -50 to 400 °C (-58 to 752 °F); Accuracy: 3 °C (5.4 °F);