Novus TxIsoRail - DIN Rail Isolated Temperature/Signal Converter

Novus TxIsoRail - DIN Rail Isolated Temperature/Signal Converter

Vendor
Novus
Regular price
£64.00 (Exc. VAT)
Sale price
£64.00 (Exc. VAT)
Regular price
£98.00 (Exc. VAT)
Sold out
Unit price
per 
Shipping calculated at checkout.

TxlsoRail is a fully programmable isolated temperature transmitter dedicated to Pt100 and thermocouple industrial sensors. TxlsoRail is a DIN rail mount unit. Both units can be easily user configured for input type and working range by means of an interface cable connected to a PC USB port.

Why use isolated transmitters?

Isolated transmitters protect the electrical instruments by eliminating ground loop effects and reduce substantially the undesirable interferences and instabilities in sensor measurements. 

TxlsoRail is two-wire signal conditioning devices that deliver 1000 Vac isolation between input and output. These devices can be fully programmed by the end user for different industrial applications. One single model can be configured to accept several thermocouple types and Pt100 RTDs. TxlsoRail can also accept O to 50 mV, 0-20 mA and 4-20 mA field signals. The flexibility of in-the-field configuration translates into a one model fits all signal conditioning and isolator module.

MPN 8806030306

Novus TxIsoRail Datasheet Download

Novus TxIsoRail-USB Manual Download

- Programmable input: thermocouples type J, K, T, E, N, R, S, B, Pt100 RTD, 0-50 mV, 0-20 mA, 4-20 mA and 0-10 V
- User programmable working range
- 2-wire loop powered 4-20 mA or 20-4 mA output
- 2 or 3-wire Pt100 input with linearized output
- Cold junction compensation for thermocouples
- Option: 0 to 10Vdc
- TxConfig Windows® configurator software
- Configuration with a PC via TxConfig interface
- Manual zero (offset) adjustment can be done by means with 1 front key in the TxIsoRail
- Power supply: 12 to 35 Vdc (4-20 mA); 18 to 30 Vdc (0-10 Vdc)
- Accuracy: Pt100, 0-50 mV (tension) and 0-20 mA (current) ±0.20% of full scale. Thermocouples ± 0.25% of full scale ± 1 °C
- Temperature effect: 0.003% of maximum SPAN/°C
- Working temperature: -40 to +85 °C (-40 to 185 °F)
- Sensor failure protection: programmable burnout upscale or downscale
- Dimensions: 72 mm (H) x 78 mm (D) x 19 mm (W)
- Isolation: 1000 Vac between sensor input and 4-20 mA output loop
- Selectable mains filter: 60 Hz or 50 Hz